Cavo ABC Di Isolamento 0,6/1kv AAAC/ACSR XLPE/PE
Informazioni di Base
Model No..
ABC Cable
Tipo
Isolato
Tipo di conduttore
Stranded
Applicazione
Alto ,
Sotterraneo
Sotterraneo
Materiale del conduttore
Alluminio
Materiale di isolamento
XLPE
Forma Materiale
Filo tondo
Certificazione
ISO9001 ,
CE ,
CCC ,
RoHS
CE ,
CCC ,
RoHS
Informazioni Aggiuntive.
Marchio
Huatong
Imballaggio
All Wooden, Steel Wooden or Steel Package
Origine
China
Codice SA
8544492100
Capacità di Produzione
5000tons /Month
Descrizione del prodotto
1. Application
0.6/1KV AAC/AAAC/ACSR XLPE/PE Insulation ABC cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
We can produce as per the standard of GB, IEC, ASTM,DIN,CSA,JIS and also particularly customize and manufacture according to your special requirement.
Standards / Testing Specifications
IEC 61089, BS 3242, DIN 48201, ASTM B399, BS EN50183, GB/T 1179-2008
Working conditions aerial insulation power cable
1) Rated voltage: 0.6kV/1Kv
2) The tallest working temperature of the cable conductor; XLPE insulation cable: 90°C;
HDPE insulation cable: 75°C;
3) During having a short (lasting less than 5 seconds) the maximum temperature;
XLPE insulated cables is 250°C;
HDPE insulated cable is 150°C
4) During the cable lying, the ambient temperature must be above-20°C
5) Bending radius allowance of the cable;
A)1Kv aerial insulation power cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more;
B) 10kV aerial insulation power cable:
Single core cable: 20 (D+d)±5%mm;
Multi-core cable:15 (D+d)±%mm
Formula inside: D-Actual cable outer diameter;
d-Actual conductor outer diameterl
Standard Packaging
As provided by standards and customer’s requirement.
0.6/1KV AAC/AAAC/ACSR XLPE/PE Insulation ABC cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
We can produce as per the standard of GB, IEC, ASTM,DIN,CSA,JIS and also particularly customize and manufacture according to your special requirement.
Standards / Testing Specifications
IEC 61089, BS 3242, DIN 48201, ASTM B399, BS EN50183, GB/T 1179-2008
Working conditions aerial insulation power cable
1) Rated voltage: 0.6kV/1Kv
2) The tallest working temperature of the cable conductor; XLPE insulation cable: 90°C;
HDPE insulation cable: 75°C;
3) During having a short (lasting less than 5 seconds) the maximum temperature;
XLPE insulated cables is 250°C;
HDPE insulated cable is 150°C
4) During the cable lying, the ambient temperature must be above-20°C
5) Bending radius allowance of the cable;
A)1Kv aerial insulation power cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more;
B) 10kV aerial insulation power cable:
Single core cable: 20 (D+d)±5%mm;
Multi-core cable:15 (D+d)±%mm
Formula inside: D-Actual cable outer diameter;
d-Actual conductor outer diameterl
Standard Packaging
As provided by standards and customer’s requirement.
BS7884-1997 | |||||
Nominal Area | Stranding | Diameter of conductor | Linear mass | Rated strength | D.C. resistance at 20°C |
mm2 | No./mm | mm | Kg/km | KN | Ω/km |
10 | 7/1.35 | 4.05 | 89.82 | 3.752 | 1.829 |
14 | 7/1.6 | 4.8 | 126.2 | 5.627 | 1.30300 |
16 | 3/2.65 | 5.72 | 148.30 | 6.194 | 1.10600 |
16 | 7/1.7 | 5.10 | 142.40 | 5.946 | 1.15400 |
25 | 7/2.1 | 6.30 | 217.30 | 9.073 | 0.75630 |
32 | 3/3.75 | 8.10 | 296.90 | 12.4 | 0.55200 |
32 | 7/2.46 | 7.38 | 298.20 | 12.442 | 0.54970 |
35 | 7/2.5 | 7.50 | 308.00 | 12.86 | 0.53370 |
50 | 7/3.00 | 9.00 | 443.50 | 18.52 | 0.37060 |
50 | 19/1.8 | 9.00 | 435.80 | 17.7 | 0.38190 |
70 | 7/3.55 | 10.65 | 621.10 | 25.93 | 0.26460 |
70 | 19/2.1 | 10.50 | 593.20 | 24.09 | 0.28060 |
95 | 19/2.5 | 12.50 | 840.70 | 34.14 | 0.19800 |
100.0 | 7/4.3 | 12.90 | 911.20 | 36.54 | 0.18100 |
120.0 | 19/2.8 | 14.00 | 1055.00 | 42.83 | 0.15780 |
125.0 | 19/2.9 | 14.50 | 1131.00 | 45.94 | 0.14710 |
150.0 | 19/3.2 | 16.00 | 1377.00 | 55.94 | 0.12080 |
150.0 | 37/2.25 | 15375.00 | 1334.00 | 53.88 | 0.12640 |
185.0 | 19/3.55 | 17.75 | 1695.00 | 68.86 | 0.09815 |
185.0 | 37/2.5 | 17.75 | 1647.00 | 66.49 | 0.10240 |
Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20 Centigrade | |||
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
No. X mm 2 | – | mm | mm | mm | mm | mm | ohm/km |
1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
Company information :
- Next: Copper/Aluminum Conductor Underground 6kv Power Cable
- Previous: 0.6/1 Kv Aerial Bundled Cable, Quadruplex XLPE Insulated Cable