Conduttore In Alluminio Di Alta Qualità Per La Cina, Cavo Abc Per Isolamento Xlpe, Cavo Antenna, Cavo Di Servizio
Informazioni di Base
Sotterraneo
CE ,
CCC ,
RoHS
Informazioni Aggiuntive.
Descrizione del prodotto
ABC cable is suitable for transmitting line and distributing line of rated voltage 0.6/1KV and others.It is widely used at tall buildings,traveling development area and rural area or other place the cost of underground network is expensive.
Code Name
ABC
Rated Voltage (Uo/U)
0.6/1KV
Temperature Range
-15ºC-90ºC
—————————————————————————————————————————–
CONSTRUCTION
Conductor: Copper or Aluminium
Insulation: XLPE
Normally,ABC Cable(ABC Bundled Cable-Aerial Cable) do not use copper,because Aluminium Cost is high,most of our customers use aluminium.
—————————————————————————————————————————–
CABLE STANDARDS
Chinese National Standards, IEC,SANS 1418-1, SANS1418-2, ASTMB230, ASTMB231,ASTM B398,ASTM B399, NF C33-209 and etc. upon request.
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01 Aerial Bundled Cable-ABC-AS NZS 3506.1
1+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
mm2 | mm | No. | ohm/km | mm2 | mm | No. | ohm/km | KN | mm | Kg/km |
1×16 | 1.3 | 6 | 1.91 | 1×16 | 1.3 | 6 | 1.91 | 4.4 | 15.0 | 140 |
1×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 7.0 | 17.6 | 210 |
1×35 | 1.5 | 6 | 0.868 | 1×35 | 1.5 | 6 | 0.868 | 9.8 | 19.6 | 270 |
1×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 14.0 | 22.8 | 370 |
1×95 | 1.7 | 15 | 0.320 | 1×95 | 1.7 | 15 | 0.320 | 26.6 | 30.6 | 680 |
2+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
mm2 | mm | No. | ohm/km | mm2 | mm | No. | ohm/km | KN | mm | Kg/km |
2×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 10.5 | 19.0 | 310 |
2×35 | 1.3 | 6 | 0.868 | 1×35 | 1.3 | 6 | 0.868 | 14.7 | 21.1 | 410 |
2×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 21.0 | 24.6 | 550 |
3+1 Structure | ||||||||||
Phase Conductor | Neutral Conductor | Completed Cable | ||||||||
Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Section | Insulation Thickness | Minimum number of wires | Max. dc resistance at 20°C | Minimum breaking load | Approx. Overall Diameter | Approx. Weight Of Cable |
3×16 | 1.3 | 6 | 1.91 | 1×16 | 1.3 | 6 | 1.91 | 8.8 | 18.1 | 290 |
3×25 | 1.3 | 6 | 1.20 | 1×25 | 1.3 | 6 | 1.20 | 14.0 | 21.2 | 410 |
3×35 | 1.3 | 6 | 0.868 | 1×35 | 1.3 | 6 | 0.868 | 19.6 | 23.7 | 550 |
3×50 | 1.5 | 6 | 0.641 | 1×50 | 1.5 | 6 | 0.641 | 28.0 | 27.5 | 740 |
3×70 | 1.5 | 12 | 0.443 | 1×70 | 1.5 | 12 | 0.443 | 39.2 | 31.9 | 1000 |
3×95 | 1.7 | 15 | 0.320 | 1×95 | 1.7 | 15 | 0.320 | 53.2 | 36.9 | 1370 |
3×120 | 1.7 | 15 | 0.253 | 1×120 | 1.7 | 15 | 0.253 | 67.2 | 40.6 | 1690 |
3×150 | 1.7 | 15 | 0.206 | 1×150 | 1.7 | 15 | 0.206 | 84.0 | 43.9 | 2020 |
BS7884-1997 |
|||||
Nominal Area |
Stranding |
Diameter of conductor |
Linear mass |
Rated strength |
D.C. resistance at 20°C |
mm2 |
No./mm |
mm |
Kg/km |
KN |
Ω/km |
10 |
7/1.35 |
4.05 |
89.82 |
3.752 |
1.829 |
14 |
7/1.6 |
4.8 |
126.2 |
5.627 |
1.30300 |
16 |
3/2.65 |
5.72 |
148.30 |
6.194 |
1.10600 |
16 |
7/1.7 |
5.10 |
142.40 |
5.946 |
1.15400 |
25 |
7/2.1 |
6.30 |
217.30 |
9.073 |
0.75630 |
32 |
3/3.75 |
8.10 |
296.90 |
12.4 |
0.55200 |
32 |
7/2.46 |
7.38 |
298.20 |
12.442 |
0.54970 |
35 |
7/2.5 |
7.50 |
308.00 |
12.86 |
0.53370 |
50 |
7/3.00 |
9.00 |
443.50 |
18.52 |
0.37060 |
50 |
19/1.8 |
9.00 |
435.80 |
17.7 |
0.38190 |
70 |
7/3.55 |
10.65 |
621.10 |
25.93 |
0.26460 |
70 |
19/2.1 |
10.50 |
593.20 |
24.09 |
0.28060 |
95 |
19/2.5 |
12.50 |
840.70 |
34.14 |
0.19800 |
100.0 |
7/4.3 |
12.90 |
911.20 |
36.54 |
0.18100 |
120.0 |
19/2.8 |
14.00 |
1055.00 |
42.83 |
0.15780 |
125.0 |
19/2.9 |
14.50 |
1131.00 |
45.94 |
0.14710 |
150.0 |
19/3.2 |
16.00 |
1377.00 |
55.94 |
0.12080 |
150.0 |
37/2.25 |
15375.00 |
1334.00 |
53.88 |
0.12640 |
185.0 |
19/3.55 |
17.75 |
1695.00 |
68.86 |
0.09815 |
185.0 |
37/2.5 |
17.75 |
1647.00 |
66.49 |
0.10240 |
Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20 Centigrade | |||
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
No. X mm 2 | – | mm | mm | mm | mm | mm | ohm/km |
1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |