N2X2y, Power Cable, 0.6/1 chilovolt, Cu/XLPE/HDPE (VDE 0276-603/HD 603 di BACCANO)
Prodotto in dettaglio
Informazioni di Base
Informazioni Aggiuntive.
Descrizione del prodotto
N2X2Y, Power Cable, 0.6/1 Kv, Cu/XLPE/HDPE (DIN VDE 0276-603/HD 603)
Underground cable with XLPE insulation and HDPE sheath
Usage:
Power distribution cables in power stations, industrial installations and switchgears, as well as in local mains. For fi xed installation underground, in interior premises, cable ducts, in the open air and in water – as permitted by the local building regulations – under severe mechanical stress during installation and operation.
Construction:
1 | Copper conductor, round stranded (RM), resp. sector-shaped stranded (SM)
2 | Core insulation (XLPE)
3 | Inner covering (EPDM)
4 | Sheath (HDPE black, UV resistant)
Standard: DIN VDE 0276-603 (HD 603)
Rated voltage: 0.6/1 kV
Test voltage: 4 kV/50 Hz
Temperature range:
laying temperature: min. -20 °C
operating temperature: -50 °C up to +90 °C
conductor temperature: max. +90 °C
short-circuit temperature: max. +250 °C/5 s
Bending radius (min. ): 12 x of cable
Core identification: Coloured (HD 308 S2)
Number of cores x nominal cross section | Max. conductor resistance | Current rating in the ground | Current rating in the air | Outer diameter | Total weight |
(mm²) | (Ω/km) | (A) | (A) | (mm) | (kg/km) |
E-XAYY | |||||
4 x 16 RM | 1.150 | 112 | 98 | 22.0 | 1020 |
4 x 25 RM | 0.727 | 145 | 133 | 26.7 | 1510 |
4 x 35 RM | 0.524 | 174 | 162 | 29.3 | 1960 |
4 x 50 SM | 0.387 | 206 | 197 | 34.4 | 2340 |
4 x 70 SM | 0.268 | 254 | 250 | 38.1 | 3,160 |
4 x 95 SM | 0.193 | 305 | 308 | 43.2 | 4,280 |
4 x 120 SM | 0.153 | 348 | 359 | 46.6 | 5,240 |
4 x 150 SM | 0.124 | 392 | 412 | 48.6 | 6,360 |
4 x 185 SM | 0.099 | 444 | 475 | 50.4 | 6,980 |
4 x 240 SM | 0.075 | 517 | 564 | 55.2 | 9,130 |