Type MP-Gc, Mining Cable, Cu/XLPE/PVC, 3/C, 5kv (ICEA S-75-381/NEMA WC-58)

 Type MP-Gc, Mining Cable, Cu/XLPE/PVC, 3/C, 5kv (ICEA S-75-381/NEMA WC-58)

Prodotto in dettaglio

Informazioni di Base

Model No.:Type MP-GC
Tipo: Isolato
Tipo di conduttore: Stranded
Applicazione: Sotterraneo
Materiale del conduttore: Rame
Materiale della guaina: PVC
Materiale di isolamento: XLPE
Forma Materiale: Filo tondo
Campo di applicazione: Miniera
Certificazione: ISO9001 , CCC

Informazioni Aggiuntive.

Marchio:DingAn or OEM
Imballaggio:Heated Steel-Wooden Drum/Steel Drum
Standard:SGS
Origine:Jiangsu Yixing, China
Codice SA:8544492100
Capacità di Produzione:38000 Km/Year

Descrizione del prodotto

Type MP-GC, Mining Cable, CU/XLPE/PVC, 3/C, 5KV (ICEA S-75-381/NEMA WC-58)

Features
True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
High voltage distribution intended for permanent installations. Suitable for underground mining and boreholes. Can be used in aerial nstallations, ducts or direct burial.

Standards
ICEA S-75-381/NEMA WC-58 Portable and Power Feeder Cables for Use in Mines and Similar Applications.

Specifications
Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures: Wet and dry locations
Normal: 90 °C
Emergency: 130 °C
Short Circuit: 250 °C

Engineering Information
1. Phase, Grounding and Ground Check Conductors: Soft or annealed uncoated copper compressed Class B stranding, or unilay-compressed per ASTM B8. On request, compacted strand. Sizes: 6 AWG up to 500 kcmil.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).

3. Insulation: Thermoset crosslinked polyethylene (XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed copper tape, 2.5 mil minimum thickness, 10% minimum overlap. Phase ID: Color printed on the extruded conducting layer, BL, WH, RE.
6. Ground Check: Thermosetting insulation yellow colored for identification.
7. Assembly: Phase conductors cabled with the ground check between the BL and WH phase conductors, two grounding conductors in inmate contact with the shields, placed on the remaining interstices, suitable fillers, as required and binder tape.

8. Jacket: Black sunlight resistance and flame retardant thermoplastic polyvinyl chloride (PVC) compound.

Conductor Size Number of Strands Size of Each Strand Nominal Insulation Thickness Ground Conductor Size Maximum Overall Diameter Approximate Total Weight
AWG or kcmil AWG mil AWG in lb/kft
6 7 90 10 110 1.3 968
4 7 90 8 110 1.4 1230
2 7 90 6 110 1.6 1620
1 19 90 5 110 1.7 1888
1/0 19 90 4 110 1.8 2211
2/0 19 90 3 140 1.9 2715
3/0 19 90 2 140 2 3219
4/0 19 90 1 140 2.2 3837
250 37 90 1/0 140 2.3 4408
300 37 90 1/0 140 2.4 5000
350 37 90 2/0 140 2.5 5746
500 37 90 4/0 140 2.9 7983