XLPE /PVC (polietilene Traversa-collegato) Insulated Electric Power Cable
Prodotto in dettaglio
Informazioni di Base
Informazioni Aggiuntive.
Descrizione del prodotto
PVC/XLPE INSULATION POWER CABLE
State Grid
ISO 9001
Internation compliance
Leading CABLE production base
Name: Copper Conductor XLPE Insulated Steel Wire Armored Power Cable
Standard: IEC60502, BS, DIN, ASTM, GB12706-2008 standard.
Voltage: Up to 35KV
Conductor: Copper or Aluminum Conductor
Insulation: PVC or XLPE
Cross Section: Based on client’s requirement
Application: Medium Voltage Power Cable is used in fixed laying to
distribute the electricity in the AC rated voltage 35kV and under 35kV transmission line.
Package: Wooden Drum Package or Iron-wooden drum
1.Brief of XLPE insulated Power Cable
XLPE insulated power cable has a number of advantages over paper insulated and PVC insulated cable.XLPE cable has high electric strength,mechanical strength,high-aging resistance,environmental stress resisting anti-chemical corrosion,and it is simple construction,using convenient and higher operating of long term temperature.It can be laid with no drop restriction.
Various of flame-retardant and non-flame retardant XLPE cable can be manufactured with three technology(peroxide,silence,and irradiation,cross linking).The flame-retardant cable covers all kinds of low-smoke,low-halogen,low-smoke halogen free and non-smoke no halogenated and three classes of A,B,C.
Our XLPE cable can be manufactured according to company’s specification which is equivalent to IEC60502,IEC60332,IEC60754.Some of indexes are superior to above international standard IEC.
Some special XLPE cable can be manufactured according to the other standards required by customers.
XLPE cable having higher long-term working temperature and greater current rating,at the same environment XLPE cable may be reduced size(nominal cross section)1 or 2 class in comparison with paper and PVC cable.These are not only improving the quality and properties of products,but also reduce cable’s production costs.
2.Scope of XLPE Cable
Type | Number of Core | Nominal Cross section of conductor mm2 |
yjv-yjlv-yjy-yjly | 1 | 1.5-1000 |
yjv22-yjlv22-yjv23-yjlv23 | ||
yjv32-yjlv32-yjv33-yjlv33 | ||
Yjv42-yjlv42-yjv43-yjlv43 | 2 | 1.5-400 |
ZR-yjv ZR-yjlv | 3 | |
ZR-yjy ZR-yjly | 4 | |
ZR-yjv22 ZR-yjlv22 | 5 | |
ZR-yjv23 ZR-yjlv23 | ||
ZR-yjv32 ZR-yjlv32 | ||
ZR-yjv33 ZR-yjlv33 | 3+1 | 2.5-400 |
ZR-yjv42 ZR-yjlv42 | 4+1 | |
ZR-yjv43 ZR-yjlv43 | 3+2 |
Note:
ZR covers three classes A,B,C of flame-retardant cable.It can be expressed as ZRA or ZRB or ZRC separately.For example:ZRB-YJV or ZRA-YJV22
Only technical data of common cable are listed in Table of Cable’s construction,weight and electrical properties.
Attached Table:Cross section area of neutral conductor in 3+1cores,4+1cores,and 3+2cores should conform to specification of following table:
Nominal Cross section mm2 | Main cores | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 |
Neutral cores | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 16 | 25 | |
Nominal Cross section mm2 | Main cores | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 |
Neutral cores | 35 | 50 | 70 | 70 | 95 | 120 | 150 | 185 |
3.Name and Type of XLPE cable
Type | Name | |
Cu core | Al core | |
YJV (YJY) |
YJLV (YJLY) |
XLPE insulated,PVC(PE)sheathed power cable |
YJV22 (YJV23) |
YJLV22 (YJLV23) |
XLPE insulated,steel tape armored,PVC(PE)sheathed power cable |
YJV32 (YJV33) |
YJLV32 (YJLV33) |
XLPE insulated,steel wire armored,PVC(PE)sheathed power cable |
YJV42 (YJV43) |
YJLV42 (YJLV43) |
XLPE insulated,thick steel wire armored,PVC(PE)sheathed power cable |
ZR-YJV (ZR-YJY) |
ZR-YJLV (ZR-YJLY) |
XLPE insulated,PVC(PE)sheathed flame-retardant power cable |
ZR-YJV22 (ZR-YJV23) |
ZR-YJLV22 (ZR-YJLV23) |
XLPE insulated,steel tape armored,PVC(PE)sheathed flame-retardant power cable |
ZR-YJV32 (ZR-YJV33) |
ZR-YJLV32 (ZR-YJLV33) |
XLPE insulated,fine steel wire armored,PVC(PE)sheathed flame-retardant power cable |
ZR-YJV42 (ZR-YJV43) |
ZR-YJLV42 (ZR-YJLV43) |
XLPE insulated,thick fine steel wire armored,PVC(PE)sheathed flame-retardant power cable |
Three-core XLPE Insulated power Cable (8.7/10 8.7/15kv) | |||||||||||||
Nominal Cross Sectional Area mm2 |
Nominal insulation thickness mm |
Approx overall diameter of cable mm |
Approx weight of cable Kg/km |
Approx overall diameter of cable mm |
Approx weight of cable Kg/km |
Approx overall diameter of cable mm |
Approx weight of cable Kg/km |
Approx overall diameter of cable mm |
Approx weight of cable Kg/km |
||||
YJV YJV |
YJLV YJLV |
YJV22 YJV23 |
YJLV22 YJLV23 |
YJV32 YJV33 |
YJLV32 YJLV33 |
YJV42 YJV43 |
YJLV42 YJLV43 |
||||||
3×25 | 4.5 | 46 | 2380 | 1901 | 50 | 3406 | 2929 | 52 | 4745 | 4262 | 55 | 6203 | 5719 |
3×35 | 4.5 | 49 | 2818 | 2132 | 53 | 3896 | 3210 | 54 | 5381 | 4589 | 59 | 6824 | 6132 |
3×50 | 4.5 | 52 | 3299 | 2405 | 56 | 4441 | 3547 | 59 | 5935 | 5030 | 61 | 8195 | 7291 |
3×70 | 4.5 | 56 | 4117 | 2818 | 59 | 5342 | 4042 | 62 | 5942 | 5631 | 65 | 8713 | 7401 |
3×95 | 4.5 | 59 | 5155 | 3294 | 64 | 6557 | 4697 | 66 | 8230 | 6352 | 69 | 10085 | 8208 |
3×120 | 4.5 | 64 | 6317 | 3892 | 69 | 7896 | 5471 | 71 | 9715 | 7266 | 74 | 11720 | 9273 |
3×150 | 4.5 | 68 | 7303 | 4366 | 73 | 8971 | 6033 | 76 | 11692 | 8728 | 78 | 12915 | 9951 |
3×185 | 4.5 | 72 | 8405 | 4880 | 76 | 10179 | 5654 | 80 | 13234 | 8677 | 82 | 14498 | 10931 |
3×240 | 4.5 | 77 | 10323 | 5728 | 82 | 12272 | 7675 | 85 | 15496 | 10859 | 87 | 16828 | 12231 |
3×300 | 4.5 | 82 | 12658 | 6691 | 88 | 15673 | 9706 | 90 | 18234 | 12213 | 92 | 19689 | 13668 |
3×400 | 4.5 | 89 | 15195 | 7767 | 96 | 18830 | 11402 | 100 | 21035 | 13607 | 103 | 22440 | 15160 |
3×500 | 4.5 | 96 | 18305 | 9020 | 104 | 22267 | 12962 | 107 | 24589 | 15304 | 110 |
Contact us