Ynky, cavo elettrico, 0.6/1 chilovolt, alto Cu/PVC/PVC ignifugo (IEC 60502-1)
Prodotto in dettaglio
Informazioni di Base
Informazioni Aggiuntive.
Descrizione del prodotto
YnKY
Underground cable with PVC insulation and PVC sheath
DESIGN
1 | Copper conductor, round solid (RE), round stranded (RM), resp. sector-shaped stranded (SM)
2 | Core insulation (PVC)
3 | Inner covering (EPDM or plastic tape)
4 | Sheath (YnKY – PVC black, higher flame retardation, UV-restistant)
APPLICATION
Power distribution cables in power stations, industrial installations and switchgears, as well as in local mains. For fi xed installation underground, in interior premises, cable ducts, in the open air, in water – as permitted by the local building regulations – if no risk of any mechanical damage is to be expected.
TECHNICAL DATA
Standard:
IEC 60502-1
Rated voltage:
0.6/1 kV
Test voltage:
3.5 kV/50 Hz
Temperature range:
laying temperature: min. -5 °C
operating temperature: -30 °C up to +70 °C
conductor temperature: max. +70 °C
short-circuit temperature: max. +160 °C/5 s
Bending radius (min.):
15 x ? of cable (single core)
12 x ? of cable (multi-core)
Core identifi cation:
HD 308 S2
Fire properties:
reduced fl ame propagation:
EN 60332-3-24 (only YnKY cable)
Number of cores x nominal cross section | Max. conductor resistance | Current rating in the ground | Current rating in the air | Outer diameter | Total weight |
(mm²) | (Ω/km) | (A) | (A) | (mm) | (kg/km) |
YnKY | |||||
3 x 1.5 RE | 12.100 | 27 | 19 | 11.6 | 210 |
4 x 1.5 RE | 12.100 | 27 | 19 | 12.4 | 245 |
5 x 1.5 RE | 12.100 | 27 | 19 | 13.3 | 280 |
3 x 2.5 RE | 7.41 | 36 | 25 | 12.5 | 260 |
4 x 2.5 RE | 7.41 | 36 | 25 | 13.4 | 305 |
5 x 2.5 RE | 7.41 | 36 | 25 | 14.4 | 355 |
3 x 4 RE | 4.610 | 47 | 34 | 14.3 | 360 |
4 x 4 RE | 4.61 | 47 | 34 | 15.4 | 425 |
5 x 4 RE | 4.61 | 47 | 34 | 16.6 | 500 |
3 x 6 RE | 3.08 | 59 | 43 | 15.3 | 445 |
4 x 6 RE | 3.08 | 59 | 43 | 16.6 | 535 |
5 x 6 RE | 3.08 | 59 | 43 | 18 | 630 |
3 x 10 RE | 1.83 | 79 | 59 | 15.3 | 610 |
4 x 10 RE | 1.83 | 79 | 59 | 18.4 | 740 |
5 x 10 RE | 1.83 | 79 | 59 | 20 | 885 |
1 x 16 RM | 1.15 | 160 | 107 | 10.9 | 225 |
3 x 16 RM | 1.15 | 102 | 79 | 20.2 | 845 |
4 x 16 RM | 1.15 | 102 | 79 | 22 | 1,030 |
5 x 16 RM | 1.15 | 102 | 79 | 24 | 1,260 |
1 x 25 RM | 0,727 | 208 | 144 | 11.8 | 335 |
4 x 25 RM | 0.727 | 133 | 106 | 25.4 | 1,490 |
5 x 25 RM | 0.727 | 133 | 106 | 28 | 1,850 |
1 x 35 RM | 0.524 | 250 | 176 | 13 | 465 |
4 x 35 SM | 0.537 | 159 | 129 | 26.4 | 1,650 |
5 x 35 RM | 0.537 | 159 | 129 | 31.2 | 2,510 |
1 x 50 RM | 0.387 | 296 | 214 | 14.6 | 610 |
4 x 50 SM | 0.387 | 188 | 157 | 31.2 | 2,230 |
5 x 50 SM | 0.387 | 188 | 157 | 36 | 3,200 |
1 x 70 RM | 0.268 | 365 | 270 | 16.4 | 815 |
4 x 70 SM | 0.268 | 232 | 199 | 34.8 | 3,070 |
5 x 70 SM | 0.268 | 232 | 199 | 40.8 | 4,360 |
1 x 95 RM | 0.193 | 438 | 334 | 18.7 | 1,120 |
4 x 95 SM | 0.193 | 280 | 246 | 40 | 4,180 |
5 x 95 SM | 0.193 | 280 | 246 | 38.4 | 5,230 |
1 x 120 RM | 0,153 | 501 | 389 | 20.2 | 1,380 |
4 x 120 SM | 0.153 | 318 | 285 | 43.6 | 5,200 |
5 x 120 SM | 0.153 | 318 | 285 | 41.9 | 6,510 |
1 x 150 RM | 0.124 | 563 | 446 | 22 | 1,610 |
4 x 150 SM | 0.124 | 359 | 326 | 46.8 | 6,310 |
5 x 150 SM | 0.124 | 359 | 326 | 46.3 | 7,970 |
1 x 185 RM | 0.099 | 639 | 516 | 24.6 | 2,020 |
4 x 185 SM | 0.099 | 406 | 374 | 53.2 | 7,830 |
5 x 185 SM | 0.099 | 406 | 374 | 51.5 | 9,900 |
1 x 240 RM | 0.075 | 746 | 618 | 27.6 | 2,610 |
4 x 240 SM | 0.075 | 473 | 445 | 58.7 | 10,280 |
5 x 240 SM | 0.075 | 473 | 445 | 57.7 | 12,860 |
1 x 300 RM | 0.06 | 845 | 711 | 30.4 | 3,260 |
1 x 400 RM | 0.047 | 975 | 843 | 34.2 | 4,220 |
1 x 500 RM | 0.037 | 1145 | 994 | 37.5 | 5,230 |
1 x 630 RM | 0.028 | 1304 | 1180 | 41.7 | 6,650 |
- Next: Cu/PVC/PVC/Awa/PVC, Power Cable, 0.6/1 Kv, 1/C (IEC 60502-1)
- Previous: Cu/XLPE/Swa/PVC, 0.6/1 Kv, Steel Wire Armored (SWA) Power Cable (IEC 60502-1)
Contact us
Simile o correlato
- No related articles