Hot Selling Cable Aluminium Core XLPE Insulation ABC Cable

 Hot Selling Cable Aluminium Core XLPE Insulation ABC Cable

Prodotto in dettaglio

Informazioni di Base

Model No.:JKLYJ
Tipo: Isolato
Tipo di conduttore: Stranded
Applicazione: Alto
Materiale del conduttore: Alluminio
Materiale della guaina: PVC
Materiale di isolamento: XLPE
Certificazione: ISO9001 , CE

Informazioni Aggiuntive.

Marchio:Jiapu
Imballaggio:Wooden Drums
Standard:any one
Origine:Henan China
Codice SA:4101962331
Capacità di Produzione:5000km/Month

Descrizione del prodotto

Hot Selling Cable Aluminium Core XLPE Insulation ABC Cable

1. Applications
Aerial Bundled cable is used for overhead power transmission and distribution lines with the voltage from 1KV-35KV. Also can be installed in the street with dense trees close to the building site of urban construction.

It consists of copper or aluminum conductor, inner shidleing layer, weather-poof indulation material and outer shidleing layer. It has not only power-transmitting chatacter of power cable, but strong mechanical chatacter of aeria; Cable as well, In compaison with bare, It boasts many advantages such as small span in laying the initiative to choose to use.

2. Standard
GB12527-90 1kv Aerial insulation cable
GB14049-93 10kv Aerial insulation cable

3. Working conditions of aerial insulation power cable
1)Rated voltage: 1kv 10kv

2)The tallest work temperatuie of the cable conductor
XLPE insulation cable temperature +90° C
HDPE insulation cable temperature +75

3)During having a short a short (lasting less than 5 seconds)
The maximum temperature
XLPE insullsted cables is temperature + 250
HDPE insulsted cables is temperature +150

4)During the cable lying the ambient temperature must be above temperature +20

5)Bending radius allowance of the cable

A)1kv aeria; Insulation power cable
It shouldbe no less than 4D for cable with outer diameter less than 25mm
It should be no less than 6D for cable with outer diameter of 25 mmor more

B)10kv aerial insulation power cable
Single core cable20(D+d )± 5%mm
Multi-core cable: 15(D+d) ± 5%mm
Formula insiide: D-Actual cable outer diameter:
D-Actual conductor outer diameter

Specifiaction:

(1)Self-supporting

Phase Phase Phase Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE Compact Conductor UV-XLPE Insulation
No.X Normal Cross Section of Cores No.of Al Wires Overall Diameter Normal Thickness Min. Diameter
No. X mm2 mm mm mm mm mm ohm/km
1 X 10 7 4.05 1.0 0.8 6.05 6.05 3.08
1 X 16 7 4.8 1.2 0.98 7.2 7.20 1.91
1 X 25 7 6 1.2 0.98 8.4 8.40 1.20
1 X 35 7 7.0 1.4 1.16 9.8 9.80 0.868
1 X 50 7 8.3 1.4 1.16 11.1 11.10 0.641
1 X 70 19 9.8 1.4 1.16 12.6 12.60 0.443
1 X 95 19 11.6 1.6 1.34 14.8 14.80 0.320
1 X 120 19 13 1.6 1.34 16.2 16.20 0.253
1 X 150 19 14.6 1.8 1.52 18.2 18.20 0.206
1 X 185 36 16.2 2.0 1.70 20.2 20.20 0.164
1 X 240 36 18.4 2.2 1.88 22.8 22.80 0.125
2 X 10 7 4.05 1.0 0.8 6.05 12.10 3.08
2 X 16 7 4.8 1.2 0.98 7.2 14.40 1.91
2 X 25 7 6 1.2 0.98 8.4 16.80 1.20
2 X 35 7 7.0 1.4 1.16 9.8 19.60 0.868
2 X 50 7 8.3 1.4 1.16 11.1 22.20 0.641
2 X 70 19 9.8 1.4 1.16 12.6 25.20 0.443
2 X 95 19 11.6 1.6 1.34 14.8 29.60 0.320
2 X 120 19 13 1.6 1.34 16.2 32.40 0.253
2 X 150 19 14.6 1.8 1.52 18.2 36.40 0.206
2 X 185 36 16.2 2.0 1.70 20.2 40.40 0.164
2 X 240 36 18.4 2.2 1.88 22.8 45.60 0.125
3 X 10 7 4.05 1.0 0.8 6.05 13.07 3.08
3 X 16 7 4.8 1.2 0.98 7.2 15.55 1.91
3 X 25 7 6 1.2 0.98 8.4 18.14 1.20
3 X 35 7 7.0 1.4 1.16 9.8 21.17 0.868
3 X 50 7 8.3 1.4 1.16 11.1 23.98 0.641
3 X 70 19 9.8 1.4 1.16 12.6 27.22 0.443
3 X 95 19 11.6 1.6 1.34 14.8 31.97 0.320
3 X 120 19 13 1.6 1.34 16.2 34.99 0.253
3 X 150 19 14.6 1.8 1.52 18.2 39.31 0.206
3 X 185 36 16.2 2.0 1.70 20.2 43.63 0.164
3 X 240 36 18.4 2.2 1.88 22.8 49.25 0.125
4 X 10 7 4.05 1.0 0.8 6.05 14.64 3.08
4 X 16 7 4.8 1.2 0.98 7.2 17.42 1.91
4 X 25 7 6 1.2 0.98 8.4 20.33 1.20
4 X 35 7 7.0 1.4 1.16 9.8 23.72 0.868
4 X 50 7 8.3 1.4 1.16 11.1 26.86 0.641
4 X 70 19 9.8 1.4 1.16 12.6 30.49 0.443
4 X 95 19 11.6 1.6 1.34 14.8 35.82 0.320
4 X 120 19 13 1.6 1.34 16.2 39.20 0.253
4 X 150 19 14.6 1.8 1.52 18.2 44.04 0.206
4 X 185 36 16.2 2.0 1.70 20.2 48.88 0.164
4 X 240 36 18.4 2.2 1.88 22.8 55.18 0.125

(2) Phase + Neutral

Phase Neutral Phase Neutral Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE AAAC Compact Conductor UV-XLPE Insulation Conductor
Phase Neutral
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.of Al.Wire Overall Dia. Normal Thickness Min. No./Dia. of Al Alloy Wire
No. X mm2 No. X mm2 mm mm Min. No./mm mm ohm/km ohm/km
1 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 12.30 1.91 2.217
1 X 25 1 X 25 7 6 1.2 0.98 7/2.10 14.70 1.20 1.393
1 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 17.30 0.868 1.007
1 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 20.10 0.641 0.744
1 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 23.10 0.443 0.514
1 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 27.30 0.320 0.371
1 X 120 1 X 120 19 13 1.6 1.34 19/2.80 30.20 0.253 0.294
1 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 33.95 0.206 0.239
1 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 37.70 0.164 0.190
1 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 43.05 0.125 0.145
2 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 14.04 1.91 2.217
2 X 25 1 X 25 7 6 1.2 0.98 7/2.10 16.63 1.20 1.393
2 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 19.51 0.868 1.007
2 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 22.46 0.641 0.744
2 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 25.70 0.443 0.514
2 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 30.31 0.320 0.371
2 X 120 1 X 120 19 13 1.6 1.34 19/2.80 33.41 0.253 0.294
2 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 37.55 0.206 0.239
2 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 41.69 0.164 0.190
2 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 47.41 0.125 0.145
3 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 16.15 1.91 2.217
3 X 25 1 X 25 7 6 1.2 0.98 7/2.10 19.06 1.20 1.393
3 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 22.32 0.868 1.007
3 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 25.59 0.641 0.744
3 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 29.22 0.443 0.514
3 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 34.42 0.320 0.371
3 X 120 1 X 120 19 13 1.6 1.34 19/2.80 37.87 0.253 0.294
3 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 42.56 0.206 0.239
3 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 47.25 0.164 0.190
3 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 53.63 0.125 0.145

(3) Phase + Neutral + Service Connection

Phase Neutral Service Connection Phase Neutral Service Connection Approx.Overall Diameter of Bundled Cable
AAC+UV-XLPE AAAC+UV-XLPE AAC+UV-XLPE Conductor UV-XLPE Conductor UV-XLPE Compact Conductor UV-XLPE
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No. of Al. Wire Overall Dia. Normal
Thickness
No./Dia. of Al. Wire Normal
Thickness
No. of Al. Wire Overall Dia. Normal
Thickness
No. X mm2 No. X mm2 No. X mm2 mm mm mm mm No./mm mm mm mm
3 X 16 1 X 50 1 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 1 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 1 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 1 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 1 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 1 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 1 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2
3 X 16 1 X 50 2 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 2 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 2 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 2 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 2 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 2 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 2 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.

Simile o correlato

  • No related articles