Soft e Hard nudi Drawn Copper Condutor Stranded Wire
Prodotto in dettaglio
Informazioni di Base
Informazioni Aggiuntive.
Descrizione del prodotto
1. Description
* Plain bare soft drawn copper conductors as per IEC 60228 class 2.
* Plain bare hard drawn Copper conductors as per DIN 48021.
2. Executive Standard
IEC 60228 class 2 & DIN 48021.
3. Application
* Soft drawn Copper conductors are used for electrical systems, where high conductively and
flexibility are required.
* Hard drawn copper conductors are used in overhead electrical distribution networks.
4. Specifications — Technical Information
Nominal Cross-sectional Area(mm2) | Construction Number/Diameter (mm) | Appro.overall Diameter(mm) | Max.D.C.resistance Of Conductor At 20ºC(Ω/km) | Appro.Weight (Kg/km) |
10 | 7/1.35 | 4.05 | 1.788 | 90 |
16 | 7/1.70 | 5.10 | 1.154 | 143 |
25 | 7/2.10 | 6.30 | 0.7563 | 218 |
35 | 7/2.50 | 7.50 | 0.530 | 310 |
50 | 7/3.00 | 9.00 | 0.371 | 445 |
70 | 19/2.15 | 10.8 | 0.268 | 624 |
95 | 19/2.52 | 12.6 | 0.194 | 857 |
120 | 19/2.85 | 14.3 | 0.152 | 1096 |
150 | 19/3.15 | 15.8 | 0.125 | 1339 |
185 | 37/2.52 | 17.6 | 0.100 | 1673 |
The above data is approximate and subjected to manufacturing tolerance.
5.SERVICING
Purpose:
To establish and maintain a procedure for performing and verifying that our service meets specified requirements and that a suitable method of feedback exists from the customer back to the appropriate individual or department within YIFANG.
Scope:
YIFANG does not currently have any contracts that obligate the company to provide installation or service above and beyond normal product service and delivery. Service activity not specified by contract (such as the treatment of a customer complaint) shall be determined and performed free of charge on a case by case basis. Service concerns will be recorded and will provide a feed-back system as required by the customer.
- Next: AAC Conductor All Aluminum Conductor ASTM B-231
- Previous: Aluminium Conductor Steel Reinforced (ACSR Overhead Cable)