Cavo antenna ABC cavo Aereo Con conduttore Messenger ACSR


                                 Cavo antenna ABC cavo Aereo Con conduttore Messenger ACSR

Informazioni di Base

Model No..
AERIAL BUNDLE CABLE

Tipo
Isolato

Tipo di conduttore
Stranded

Applicazione
Alto ,
Sotterraneo

Materiale del conduttore
Alluminio

Materiale di isolamento
XLPE

Forma Materiale
Filo tondo

Certificazione
ISO9001 ,
CE ,
CCC ,
RoHS

Informazioni Aggiuntive.

Marchio
Huatong

Imballaggio
All Wooden, Steel Wooden or Steel Package

Origine
China

Codice SA
8544492100

Capacità di Produzione
5000tons /Month

Descrizione del prodotto

ABC Aerial overhead cable with ACSR messenger Core

ABC cable is suitable for transmitting line and distributing line of rated voltage 0.6/1KV and others.It is widely used at tall buildings,traveling development area and rural area or other place the cost of underground network is expensive.
 

Basic Information
Code Name
ABC
Rated Voltage (Uo/U)
0.6/1KV
Temperature Range
-15ºC-90ºC

—————————————————————————————————————————–

CONSTRUCTION
Conductor: Copper or Aluminium
Insulation: XLPE
Normally,ABC Cable(ABC Bundled Cable-Aerial Cable) do not use copper,because Aluminium Cost is high,most of our customers use aluminium.
—————————————————————————————————————————–

CABLE STANDARDS
Chinese National Standards, IEC,SANS 1418-1, SANS1418-2, ASTMB230, ASTMB231,ASTM B398,ASTM B399, NF C33-209 and etc. upon request.

—————————————————————————————————————————–

Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1

Table 01 Aerial Bundled Cable-ABC-AS NZS 3506.1
 

1+1 Structure
Phase Conductor Neutral Conductor Completed Cable
Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Minimum breaking load Approx. Overall Diameter Approx. Weight Of Cable
mm2 mm No. ohm/km mm2 mm No. ohm/km KN mm Kg/km
1×16 1.3 6 1.91 1×16 1.3 6 1.91 4.4 15.0 140
1×25 1.3 6 1.20 1×25 1.3 6 1.20 7.0 17.6 210
1×35 1.5 6 0.868 1×35 1.5 6 0.868 9.8 19.6 270
1×50 1.5 6 0.641 1×50 1.5 6 0.641 14.0 22.8 370
1×95 1.7 15 0.320 1×95 1.7 15 0.320 26.6 30.6 680
2+1 Structure
Phase Conductor Neutral Conductor Completed Cable
Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Minimum breaking load Approx. Overall Diameter Approx. Weight Of Cable
mm2 mm No. ohm/km mm2 mm No. ohm/km KN mm Kg/km
2×25 1.3 6 1.20 1×25 1.3 6 1.20 10.5 19.0 310
2×35 1.3 6 0.868 1×35 1.3 6 0.868 14.7 21.1 410
2×50 1.5 6 0.641 1×50 1.5 6 0.641 21.0 24.6 550
3+1 Structure
Phase Conductor Neutral Conductor Completed Cable
Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Section Insulation Thickness Minimum number of wires Max. dc resistance at 20°C Minimum breaking load Approx. Overall Diameter Approx. Weight Of Cable
3×16 1.3 6 1.91 1×16 1.3 6 1.91 8.8 18.1 290
3×25 1.3 6 1.20 1×25 1.3 6 1.20 14.0 21.2 410
3×35 1.3 6 0.868 1×35 1.3 6 0.868 19.6 23.7 550
3×50 1.5 6 0.641 1×50 1.5 6 0.641 28.0 27.5 740
3×70 1.5 12 0.443 1×70 1.5 12 0.443 39.2 31.9 1000
3×95 1.7 15 0.320 1×95 1.7 15 0.320 53.2 36.9 1370
3×120 1.7 15 0.253 1×120 1.7 15 0.253 67.2 40.6 1690
3×150 1.7 15 0.206 1×150 1.7 15 0.206 84.0 43.9 2020

 

ABC Aerial overhead cable with ACSR messenger Core
Nominal csetion area(sqmm)
Conductor structure
Insulation material
Insulation Thickness(mm)
Approx. Overall Diameter(mm)
Approx. weight
(kg/km)
Packing meters per drum
Phase
(Compacted AL)
Neutral
(bare ACSR)
(No./mm)
Aluminum
(No./mm)
Steel
(No./mm)
1×16+16
7/1.72
6/1.72
1/1.72
XLPE
1.2
12.5
121.9
250-4000m
1×25+25
7/2.15
6/2.15
1/2.15
 
1.2
14.9
182.2
250-4000
1×35+35
7/2.54
6/2.54
1/2.54
 
1.4
17.5
254.7
250-3500m
1×70+70
19/2.15
12/2.15
7/2.15
 
1.4
23.6
382.2
250-3000m
1×95+95
19/2.54
12/2.54
7/2.54
 
1.6
27.6
528.2
250-3000m
2×16+16
7/1.72
6/1.72
1/1.72
 
1.2
14.2
187.6
250-4000m
2×25+25
7/2.15
6/2.15
1/2.15
 
1.2
16.7
273.8
250-3500m
2×35+35
7/2.54
6/2.54
1/2.54
 
1.4
19.7
386.9
250-3500m
2×70+70
19/2.15
12/2.15
7/2.15
 
1.4
26.1
617.2
250-3000m
2×95+95
19/2.54
12/2.54
7/2.54
 
1.6
30.5
850.9
250-3500m
3×70+70
19/2.15
12/2.15
7/2.15
 
1.4
29.7
1024.3
250-3000m
3×95+95
19/2.54
12/2.54
7/2.54
 
1.6
34.6
1413.7
250-3000m

 

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.