Primary Ud Cable, 35 Kv, Al/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)

 Primary Ud Cable, 35 Kv, Al/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)

Prodotto in dettaglio

Informazioni di Base

Model No.:Primary UD Cable
Applicazione: Sotterraneo
Voltaggio: Cavo a bassa tensione e media
Corrente: Cavo DC
Materiale di isolamento: XLPE
Forma Materiale: Filo tondo
Certificazione: ISO , CCC

Informazioni Aggiuntive.

Marchio:DingAn or OEM
Imballaggio:Heated Steel-Wooden Drum/Steel Drum
Standard:SGS
Origine:Jiangsu Yixing, China
Codice SA:8544601200
Capacità di Produzione:12000 Km/Year

Descrizione del prodotto

Primary UD Cable, 35 KV, AL/TR-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Applications:
Predominantly used for primary underground distribution; Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15, 000 volts or less and at conductor temperatures not to exceed 90° C for normal operation.
Specifications:
Primary UD Cable meets or exceeds the following ASTM specifications:
B-3 Soft Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:
ANSI/ICEA S-94-649
AEIC CS-8
RUS U-1
Construction:
The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting polyethylene jacket is available upon request.
Maximum Conductor Normal Operation: – 90O C;
Emergency Overload: – 130O C
Temperatures: Short Circuit – 250 C
Application: Medium voltage power cable for single phase underground distribution (UD), including getaway systems in low profile substations.

1/3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Aluminum 100% Insulation Level (345 mil)
1/0 1 1.06 6 14 50 1.38 757 1/0 1 1.06 16 14 50 1.38 878
1/0 19 1.10 6 14 50 1.42 789 1/0 19 1.10 16 14 50 1.42 910
2/0 19 1.14 7 14 50 1.47 859 2/0 19 1.14 20 14 50 1.47 1016
3/0 19 1.19 9 14 50 1.52 951 2/0 19 1.14 13 12 50 1.50 1055
4/0 19 1.25 11 14 50 1.57 1057 3/0 19 1.19 25 14 50 1.52 1144
250 37 1.30 13 14 80 1.69 1223 3/0 19 1.19 16 12 50 1.55 1181
350 37 1.40 18 14 80 1.79 1454 4/0 19 1.25 32 14 50 1.57 1310
500 37 1.53 25 14 80 1.95 1822 4/0 19 1.25 20 12 50 1.61 1341
500 37 1.53 16 12 80 1.99 1868 4/0 19 1.25 13 10 80 1.71 1465
750 61 1.74 24 12 80 2.19 2431 250 37 1.30 25 12 80 1.73 1582
750 61 1.74 15 10 80 2.24 2488 250 37 1.30 16 10 80 1.77 1637
1000 61 1.89 31 12 80 2.34 2921 350 37 1.40 32 12 80 1.83 1889
1000 61 1.89 20 10 80 2.38 3000 350 37 1.40 20 10 80 1.87 1935
1000 61 1.89 16 9 80 2.41 3043 350 37 1.40 16 9 80 1.89 1970
500 37 1.53 29 10 80 2.03 2500
750 61 1.74 28 8 80 2.29 3464
1000 61 1.89 37 8 80 2.44 4265
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 50 1.57 934 1/0 19 1.25 16 14 50 1.57 1054
2/0 19 1.29 7 14 50 1.62 1008 2/0 19 1.29 13 12 80 1.71 1275
3/0 19 1.34 9 14 80 1.73 1173 3/0 19 1.34 16 12 80 1.76 1408
4/0 19 1.40 11 14 80 1.79 1287 4/0 19 1.40 13 10 80 1.86 1638
250 37 1.45 13 14 80 1.84 1394 250 37 1.45 16 10 80 1.92 1815
350 37 1.56 18 14 80 1.98 1681 350 37 1.56 16 9 80 2.08 2208
500 37 1.68 25 14 80 2.11 2018
500 37 1.68 16 12 80 2.14 2068
750 61 1.89 24 12 80 2.34 2650
750 61 1.89 15 10 80 2.39 2710
1000 61 2.04 16 9 80 2.56 3282